Cooling Systems
Air cooling limits, direct liquid cooling, rear-door heat exchangers, immersion cooling β capacity, cost, and retrofit feasibility.
Cooling is the physical constraint that determines how many GPUs you can pack into a rack. Air cooling maxes out at ~25 kW/rack. Modern GPU racks need 40-120 kW. Direct liquid cooling (DLC) is no longer optional for dense AI deployments β itβs a requirement.
1. Cooling Capacity by Method
| Method | Max rack power | PUE | Upfront cost | Retrofit difficulty |
|---|---|---|---|---|
| Air cooling (CRAC/CRAH) | 15-25 kW | 1.3-1.6 | Low | N/A (default) |
| Rear-door heat exchanger | 25-40 kW | 1.1-1.3 | Medium | Easy (bolt-on) |
| Direct liquid cooling (DLC) | 60-120+ kW | 1.05-1.15 | High | Moderate (piping) |
| Immersion cooling | 100+ kW | 1.02-1.08 | Highest | Hard (tanks) |
2. Air Cooling
Hot air from servers rises, gets cooled by CRAC/CRAH units, and recirculates:
Server β Hot aisle (35-45Β°C) β CRAH unit β Cold aisle (18-27Β°C) β Server
Optimization
| Technique | Benefit |
|---|---|
| Hot/cold aisle containment | Prevents mixing, +2-3 kW/rack capacity |
| Raised floor with directed airflow | Better distribution |
| Variable-speed fans | Reduce energy at low load |
| Higher inlet temperature (27Β°C vs 18Β°C) | Reduce cooling energy, more free cooling hours |
Hard limit: Air cooling fundamentally cannot handle >~25 kW/rack. The air canβt carry enough heat away. For H100/B200 racks, air alone is insufficient.
3. Direct Liquid Cooling (DLC)
Cold plates on GPUs and CPUs carry heat to a Coolant Distribution Unit (CDU):
GPU cold plate β warm coolant (40-45Β°C) β CDU β cooling tower/chiller β cold coolant (25-30Β°C) β GPU
Why DLC for AI
| Advantage | Impact |
|---|---|
| 3-5Γ cooling capacity per rack | Supports 40-120 kW racks |
| GPU runs cooler (50-65Β°C vs 75-85Β°C) | Less thermal throttling, longer lifespan |
| Lower PUE (1.05-1.15) | 15-20% less total power |
| Quieter (fewer fans) | Better working environment |
| Smaller footprint | More racks per floor |
DLC Components
Per-rack:
βββ Cold plates (on each GPU + CPU): $500-1000/server
βββ Quick-connect manifolds: $2,000-5,000/rack
βββ Flexible hoses: $500-1,000/rack
Per-row:
βββ CDU (Coolant Distribution Unit): $30,000-80,000
βββ Heat exchanger (liquid-to-liquid or liquid-to-air)
βββ Pumps (redundant)
βββ Monitoring (flow rate, temperature, pressure)
Facility:
βββ Cooling tower or chiller plant connection
βββ Piping infrastructure
βββ Water treatment system
GB200 NVL72 Rack Cooling
GB200 NVL72 rack: 120 kW total
βββ 72 GPUs with integrated cold plates
βββ 36 Grace CPUs with cold plates
βββ NVSwitch trays with cold plates
βββ Single-phase liquid cooling manifold at rack level
Coolant: facility water (25-45Β°C) or propylene glycol mix
Flow rate: ~60-80 liters/minute per rack
4. Rear-Door Heat Exchangers (RDHx)
A retrofit option that extends air-cooled racks to ~40 kW:
Server exhausts hot air β rear-door water coil captures heat β cooled air exits
Pros: Easy retrofit (replace rear door), no server modification.
Cons: Limited to ~40 kW, still needs some room air cooling, water near servers.
5. Immersion Cooling
Servers submerged in dielectric fluid:
Single-phase: Servers in fluid bath β fluid circulated to external heat exchanger
Two-phase: Fluid boils on hot components β vapor condenses on coils β drips back
| Property | Single-phase | Two-phase |
|---|---|---|
| Fluid | Mineral oil, synthetic | Engineered fluids (3M Novec) |
| Max density | 100+ kW/tank | 100+ kW/tank |
| PUE | 1.03-1.06 | 1.02-1.05 |
| Maintenance | Messy (oil) | Cleaner but expensive fluid |
| Server compatibility | Standard servers (with mods) | Requires specific design |
| Cost per kW | High | Very high |
Best for: Extreme density, harsh environments (dust, heat), or locations without water.
6. Decision Matrix
Rack power needed:
βββ <15 kW (T4, light CPU): Air cooling sufficient
βββ 15-25 kW (A100, sparse): Air + hot/cold containment
βββ 25-40 kW (H100, moderate): Rear-door heat exchanger OR DLC
βββ 40-80 kW (H100 dense): DLC required
βββ 80-120+ kW (GB200 NVL72): DLC required (factory-integrated)
New build vs retrofit:
βββ New construction β DLC from day 1 (easiest, cheapest long-term)
βββ Existing facility β RDHx for quick upgrade, DLC for long-term
βββ Extreme density β Immersion if floor loading supports it
Self-Check
- Calculate why air cooling fails above 25 kW/rack
- Design a DLC system for a row of H100 racks including CDU and piping
- Compare RDHx vs DLC for retrofitting an existing air-cooled facility
- Estimate PUE improvement from switching air cooling to DLC
- Evaluate immersion cooling for a GB200 deployment
References
- NVIDIA DLC Deployment Guide
- ASHRAE TC9.9: Thermal Guidelines for Data Processing Environments
- For power delivery, see Power Delivery
- For rack layout, see Physical Topology