Cooling Systems

Air cooling limits, direct liquid cooling, rear-door heat exchangers, immersion cooling β€” capacity, cost, and retrofit feasibility.

coolingliquid-coolingdlcimmersionair-coolingpue

Cooling is the physical constraint that determines how many GPUs you can pack into a rack. Air cooling maxes out at ~25 kW/rack. Modern GPU racks need 40-120 kW. Direct liquid cooling (DLC) is no longer optional for dense AI deployments β€” it’s a requirement.


1. Cooling Capacity by Method

MethodMax rack powerPUEUpfront costRetrofit difficulty
Air cooling (CRAC/CRAH)15-25 kW1.3-1.6LowN/A (default)
Rear-door heat exchanger25-40 kW1.1-1.3MediumEasy (bolt-on)
Direct liquid cooling (DLC)60-120+ kW1.05-1.15HighModerate (piping)
Immersion cooling100+ kW1.02-1.08HighestHard (tanks)

2. Air Cooling

Hot air from servers rises, gets cooled by CRAC/CRAH units, and recirculates:

Server β†’ Hot aisle (35-45Β°C) β†’ CRAH unit β†’ Cold aisle (18-27Β°C) β†’ Server

Optimization

TechniqueBenefit
Hot/cold aisle containmentPrevents mixing, +2-3 kW/rack capacity
Raised floor with directed airflowBetter distribution
Variable-speed fansReduce energy at low load
Higher inlet temperature (27Β°C vs 18Β°C)Reduce cooling energy, more free cooling hours

Hard limit: Air cooling fundamentally cannot handle >~25 kW/rack. The air can’t carry enough heat away. For H100/B200 racks, air alone is insufficient.


3. Direct Liquid Cooling (DLC)

Cold plates on GPUs and CPUs carry heat to a Coolant Distribution Unit (CDU):

GPU cold plate β†’ warm coolant (40-45Β°C) β†’ CDU β†’ cooling tower/chiller β†’ cold coolant (25-30Β°C) β†’ GPU

Why DLC for AI

AdvantageImpact
3-5Γ— cooling capacity per rackSupports 40-120 kW racks
GPU runs cooler (50-65Β°C vs 75-85Β°C)Less thermal throttling, longer lifespan
Lower PUE (1.05-1.15)15-20% less total power
Quieter (fewer fans)Better working environment
Smaller footprintMore racks per floor

DLC Components

Per-rack:
  β”œβ”€β”€ Cold plates (on each GPU + CPU): $500-1000/server
  β”œβ”€β”€ Quick-connect manifolds: $2,000-5,000/rack
  └── Flexible hoses: $500-1,000/rack

Per-row:
  └── CDU (Coolant Distribution Unit): $30,000-80,000
      β”œβ”€β”€ Heat exchanger (liquid-to-liquid or liquid-to-air)
      β”œβ”€β”€ Pumps (redundant)
      └── Monitoring (flow rate, temperature, pressure)

Facility:
  └── Cooling tower or chiller plant connection
      β”œβ”€β”€ Piping infrastructure
      └── Water treatment system

GB200 NVL72 Rack Cooling

GB200 NVL72 rack: 120 kW total
  β”œβ”€β”€ 72 GPUs with integrated cold plates
  β”œβ”€β”€ 36 Grace CPUs with cold plates  
  β”œβ”€β”€ NVSwitch trays with cold plates
  └── Single-phase liquid cooling manifold at rack level

Coolant: facility water (25-45Β°C) or propylene glycol mix
Flow rate: ~60-80 liters/minute per rack

4. Rear-Door Heat Exchangers (RDHx)

A retrofit option that extends air-cooled racks to ~40 kW:

Server exhausts hot air β†’ rear-door water coil captures heat β†’ cooled air exits

Pros: Easy retrofit (replace rear door), no server modification.
Cons: Limited to ~40 kW, still needs some room air cooling, water near servers.


5. Immersion Cooling

Servers submerged in dielectric fluid:

Single-phase: Servers in fluid bath β†’ fluid circulated to external heat exchanger
Two-phase: Fluid boils on hot components β†’ vapor condenses on coils β†’ drips back
PropertySingle-phaseTwo-phase
FluidMineral oil, syntheticEngineered fluids (3M Novec)
Max density100+ kW/tank100+ kW/tank
PUE1.03-1.061.02-1.05
MaintenanceMessy (oil)Cleaner but expensive fluid
Server compatibilityStandard servers (with mods)Requires specific design
Cost per kWHighVery high

Best for: Extreme density, harsh environments (dust, heat), or locations without water.


6. Decision Matrix

Rack power needed:
β”œβ”€β”€ <15 kW (T4, light CPU):      Air cooling sufficient
β”œβ”€β”€ 15-25 kW (A100, sparse):     Air + hot/cold containment
β”œβ”€β”€ 25-40 kW (H100, moderate):   Rear-door heat exchanger OR DLC
β”œβ”€β”€ 40-80 kW (H100 dense):       DLC required
└── 80-120+ kW (GB200 NVL72):    DLC required (factory-integrated)

New build vs retrofit:
β”œβ”€β”€ New construction β†’ DLC from day 1 (easiest, cheapest long-term)
β”œβ”€β”€ Existing facility β†’ RDHx for quick upgrade, DLC for long-term
└── Extreme density β†’ Immersion if floor loading supports it

Self-Check

  • Calculate why air cooling fails above 25 kW/rack
  • Design a DLC system for a row of H100 racks including CDU and piping
  • Compare RDHx vs DLC for retrofitting an existing air-cooled facility
  • Estimate PUE improvement from switching air cooling to DLC
  • Evaluate immersion cooling for a GB200 deployment